Lighting CalculatorPlan light with clear assumptions

Lighting calculators / Rooms & layouts

Plan the light. Understand the numbers.

Lighting calculator

Estimate room lighting, compare light units and plan LED power. Start with the lumen method below, or explore 37 focused calculators with worked tables and published references.

Your lighting inputs

m
m
lux
lm
ratio
ratio

Starting values are illustrative. Check units and assumptions below. Calculate submits your inputs to this site’s result page.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

Required fixtures = ceiling(target lux × area ÷ (fixture lumens × CU × LLF)).

Use the lumen method to estimate fixture count for a chosen maintained average light level.

  1. Choose a measurement plane and use compatible units for all inputs.
  2. Obtain appropriate product data or representative measurements for the stated model.
  3. Submit the form, then interpret the result with the assumptions and limits below.

CU and LLF must fit the luminaire, room and maintenance plan. This average method cannot establish point uniformity, glare or code compliance.

How many lumens and light fixtures does a room need?

A room lumen calculation starts with the light level required on a defined working plane and its area. Lux multiplied by square metres gives the luminous flux arriving at that plane. More initial fixture lumens are normally required because some light misses the useful area and output can decline between maintenance visits. The coefficient of utilization and light loss factor keep those effects explicit.

Use this approach for a living room, kitchen, office, garage, shop or warehouse when the assumptions are meaningful. The 300 lux starting value is a chosen example, not a universal room recommendation. High ceilings, shelving, dark finishes and task needs affect the appropriate design. Recessed fixtures, high bays and chandeliers need their own product data; the room name alone does not determine their spacing or output.

Check the numbers

Room Lighting Calculator: calculated examples

These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.

Worked example with stated inputs

Room length = 5 m; Room width = 4 m; Target maintained illuminance = 300 lux; Initial output per luminaire = 1800 lm; Coefficient of utilization = 0.6 ratio; Light loss factor = 0.8 ratio.

OutputComputed result
Estimated whole fixture count7 fixtures
Room area20 m²
Delivered target flux6,000 lm
Initial installed lumens12,600 lm
Modeled maintained average302.4 lux

How one input changes the answer

ScenarioChanged inputResult
1.25 mRoom length2 fixtures
2.5 mRoom length4 fixtures
3.75 mRoom length6 fixtures
5 mRoom length7 fixtures
7.5 mRoom length11 fixtures
10 mRoom length14 fixtures
15 mRoom length21 fixtures

Unchanged inputs use: Room length = 5 m; Room width = 4 m; Target maintained illuminance = 300 lux; Initial output per luminaire = 1800 lm; Coefficient of utilization = 0.6 ratio; Light loss factor = 0.8 ratio. Results retain the model limitations described above.

Common questions

How do I calculate lumens needed for a room?

Multiply target lux by room area for delivered work-plane lumens, then divide by CU and LLF for initial installed fixture lumens. Divide that by per-fixture output and round the fixture count upward.

Can I use square feet instead of square metres?

Convert area in ft² to m² by multiplying by 0.09290304. One foot-candle is one lumen per square foot; use the illuminance converter to change the target unit.

Is this suitable for kitchen, shop or office lighting?

It estimates average maintained illuminance with your target and product data. Task lighting, vertical surfaces, shadows and glare still require separate review.

Does this replace DIALux, Relux, AGi32 or Revit?

No. It does not import IES/LDT files, trace reflections, model obstacles or produce a compliant photometric plan. It provides a transparent hand-calculation starting point.

Can I convert lumens to kelvin?

No. Lumens measure luminous flux and kelvin describes color temperature. Neither value determines the other.

Can I export a lighting calculation report or Excel sheet?

Use the visible formula and worked values in a worksheet, or print the page. There is no PDF report generator, Revit plugin or downloadable design software.

Does this enforce IEC, IES or adopted building requirements?

No. The applicable target, measurement plane, maintenance basis and compliance procedure must be established for the project. This hand calculation does not select a current standard or certify compliance.

Which assumptions should I check?

Match the units, measurement plane and equipment boundary stated on this page. The starting values and comparison cases are chosen examples, not universal recommendations or current manufacturer ratings.

Where are the formula references?

Published references are listed at the bottom of this page as plain-text website addresses. The example tables are calculated from the displayed method rather than copied from proprietary tables.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.

  • UC Davis California Lighting Technology Center: High-Efficacy Residential Lighting, lumen method and room cavity ratiohttps://cltc.ucdavis.edu/sites/g/files/dgvnsk12206/files/media/documents/high-efficacy-residential-lighting-guide-dec14.pdf
  • NIST SP 811 Appendix B.9: photometric unit conversionshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9