Lighting CalculatorPlan light with clear assumptions

Lighting calculators / LED circuits & power

Plan the light. Understand the numbers.

Connected Lighting Load Calculator

Summing full-luminaire input gives a real connected load. If the drivers have a known true power factor, dividing real watts by that factor gives an aggregate apparent-power estimate under the stated simplifying assumption. A complete installation can behave differently when drivers operate at different load levels.

Your lighting inputs

fixtures
W
V
ratio

Starting values are illustrative. Check units and assumptions below. Calculate submits your inputs to this site’s result page.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

Real input W = count × fixture W; apparent VA = W/PF; single-phase A = VA/V.

Estimate real and apparent connected lighting loads from fixture input and true power factor.

  1. Choose a measurement plane and use compatible units for all inputs.
  2. Obtain appropriate product data or representative measurements for the stated model.
  3. Submit the form, then interpret the result with the assumptions and limits below.

This steady connected-load estimate excludes inrush, harmonics, branch-circuit rules and diversity. Use actual full-product input data.

LED lighting watts, VA and steady current

Summing full-luminaire input gives a real connected load. If the drivers have a known true power factor, dividing real watts by that factor gives an aggregate apparent-power estimate under the stated simplifying assumption. A complete installation can behave differently when drivers operate at different load levels.

The current shown is not a breaker or contactor selection. LED inrush and switching conditions may matter even when steady current is modest. For different luminaire types, calculate each group with appropriate data and combine compatible real/apparent quantities carefully.

Check the numbers

Connected Lighting Load Calculator: calculated examples

These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.

Worked example with stated inputs

Identical luminaires = 10 fixtures; Input per complete luminaire = 18 W; Single-phase voltage = 230 V; True power factor = 0.9 ratio.

OutputComputed result
Real connected lighting input180 W
Apparent connected load200 VA
Simple steady single-phase current0.869565 A

How one input changes the answer

ScenarioChanged inputResult
2 fixturesIdentical luminaires36 W
5 fixturesIdentical luminaires90 W
8 fixturesIdentical luminaires144 W
10 fixturesIdentical luminaires180 W
15 fixturesIdentical luminaires270 W
20 fixturesIdentical luminaires360 W
30 fixturesIdentical luminaires540 W

Unchanged inputs use: Identical luminaires = 10 fixtures; Input per complete luminaire = 18 W; Single-phase voltage = 230 V; True power factor = 0.9 ratio. Results retain the model limitations described above.

Common questions

Should I use LED chip watts or wall-input watts?

Use the complete luminaire’s electrical input, including its driver at the chosen operating point.

Does this account for inrush?

No. Obtain startup and switching data for the actual drivers and control equipment.

Can I use this for three-phase circuits?

The current equation here is single phase. It does not determine balancing or three-phase circuit arrangements.

Does power factor affect lumen output directly?

Power factor is an electrical relationship. It does not by itself specify photometric output or color quality.

Which assumptions should I check?

Match the units, measurement plane and equipment boundary stated on this page. The starting values and comparison cases are chosen examples, not universal recommendations or current manufacturer ratings.

Where are the formula references?

Published references are listed at the bottom of this page as plain-text website addresses. The example tables are calculated from the displayed method rather than copied from proprietary tables.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.

  • NIST SP 811 Appendix B.9: photometric unit conversionshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9
  • MEAN WELL: LED Driver Power Supply Solution, operating limits and loadinghttps://led.meanwell.com/qa.aspx?c=10