Lighting CalculatorPlan light with clear assumptions

Lighting calculators / LED circuits & power

Plan the light. Understand the numbers.

Lighting Power Density Calculator

Lighting power density is input power per area, not a light level. Include the equipment boundary required by the method you are using, such as driver losses when they form part of connected input. A low W/m² figure alone cannot show that task illuminance or visual quality is adequate.

Your lighting inputs

W
m²
W/m²

Starting values are illustrative. Check units and assumptions below. Calculate submits your inputs to this site’s result page.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

LPD = total connected lighting input watts ÷ floor area; W/ft² = W/m² × 0.09290304.

Calculate lighting power density and compare it with an explicitly supplied allowance.

  1. Choose a measurement plane and use compatible units for all inputs.
  2. Obtain appropriate product data or representative measurements for the stated model.
  3. Submit the form, then interpret the result with the assumptions and limits below.

This does not select an NEC, NCC, Section J or other code limit. Exemptions, controls, adjusted allowances and adopted editions require separate verification.

LPD, NCC Section J and lighting compliance worksheets

Lighting power density is input power per area, not a light level. Include the equipment boundary required by the method you are using, such as driver losses when they form part of connected input. A low W/m² figure alone cannot show that task illuminance or visual quality is adequate.

For Australian NCC 2022 or 2025 and Section J/J7 searches, first establish the adopted provision, building class, calculation method and applicable adjustments. The comparison allowance here is entered by the visitor. This website does not reproduce the code, determine a jurisdiction’s adoption or issue a compliance calculation form.

Check the numbers

Lighting Power Density Calculator: calculated examples

These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.

Worked example with stated inputs

Total lighting input = 200 W; Area = 20 m²; Chosen comparison allowance = 10 W/m².

OutputComputed result
Connected lighting power density10 W/m²
Same density0.92903 W/ft²
Percentage of chosen allowance100 %

How one input changes the answer

ScenarioChanged inputResult
50 WTotal lighting input2.5 W/m²
100 WTotal lighting input5 W/m²
150 WTotal lighting input7.5 W/m²
200 WTotal lighting input10 W/m²
300 WTotal lighting input15 W/m²
400 WTotal lighting input20 W/m²
600 WTotal lighting input30 W/m²

Unchanged inputs use: Total lighting input = 200 W; Area = 20 m²; Chosen comparison allowance = 10 W/m². Results retain the model limitations described above.

Common questions

Does LPD tell me room brightness?

No. Brightness-related metrics and delivered illuminance also depend on efficacy, distribution and the room.

Is the default 10 W/m² a code limit?

No. It is an illustrative comparison input, not a claim about any current regulation.

Can I calculate a percentage of allowance?

Yes. Divide calculated W/m² by a positive allowance and multiply by 100; the result is arithmetic under the stated allowance.

Does this certify NCC or NEC compliance?

No. It does not determine adopted editions, exemptions or the complete compliance pathway.

Which assumptions should I check?

Match the units, measurement plane and equipment boundary stated on this page. The starting values and comparison cases are chosen examples, not universal recommendations or current manufacturer ratings.

Where are the formula references?

Published references are listed at the bottom of this page as plain-text website addresses. The example tables are calculated from the displayed method rather than copied from proprietary tables.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.

  • UC Davis California Lighting Technology Center: High-Efficacy Residential Lighting, lumen method and room cavity ratiohttps://cltc.ucdavis.edu/sites/g/files/dgvnsk12206/files/media/documents/high-efficacy-residential-lighting-guide-dec14.pdf
  • NIST SP 811 Appendix B.9: photometric unit conversionshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9