Lighting CalculatorPlan light with clear assumptions

Lighting calculators / Energy & project costs

Plan the light. Understand the numbers.

Emergency Lighting Energy Calculator

An energy budget estimates storage needed to support the entered electrical load for a stated time. That does not establish the minimum light level along an escape route or the performance at the end of discharge. The default duration is an example supplied to the model, not a legal requirement for every jurisdiction.

Your lighting inputs

W
hours
V
%
%

Starting values are illustrative. Check units and assumptions below. Calculate submits your inputs to this site’s result page.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

Nominal battery Wh = output W × hours ÷ usable fraction ÷ efficiency; Ah = nominal Wh ÷ nominal V.

Calculate a simplified emergency lighting battery energy budget for an explicitly chosen duration.

  1. Choose a measurement plane and use compatible units for all inputs.
  2. Obtain appropriate product data or representative measurements for the stated model.
  3. Submit the form, then interpret the result with the assumptions and limits below.

No emergency lighting code duration or compliance result is supplied. Battery discharge behavior, end-of-life margins, actual luminaire output and product certification need separate assessment.

Emergency lighting runtime is separate from evacuation illuminance

An energy budget estimates storage needed to support the entered electrical load for a stated time. That does not establish the minimum light level along an escape route or the performance at the end of discharge. The default duration is an example supplied to the model, not a legal requirement for every jurisdiction.

DIALux, Relux and certified emergency luminaires may support more complete photometric and product-specific checks. This tool does not reproduce those processes. Enter appropriate battery voltage, usable energy and conversion efficiency, then verify ratings and maintained output with the actual manufacturer documentation.

Check the numbers

Emergency Lighting Energy Calculator: calculated examples

These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.

Worked example with stated inputs

Continuous emergency lighting output load = 20 W; Required duration supplied by designer = 3 hours; Nominal battery voltage = 12 V; Usable nominal energy = 80 %; Conversion efficiency = 90 %.

OutputComputed result
Nominal battery energy budget83.333333 Wh
Nominal charge capacity6.944444 Ah
Required output energy60 Wh

How one input changes the answer

ScenarioChanged inputResult
5 WContinuous emergency lighting output load20.833333 Wh
10 WContinuous emergency lighting output load41.666667 Wh
15 WContinuous emergency lighting output load62.5 Wh
20 WContinuous emergency lighting output load83.333333 Wh
30 WContinuous emergency lighting output load125 Wh
40 WContinuous emergency lighting output load166.666667 Wh
60 WContinuous emergency lighting output load250 Wh

Unchanged inputs use: Continuous emergency lighting output load = 20 W; Required duration supplied by designer = 3 hours; Nominal battery voltage = 12 V; Usable nominal energy = 80 %; Conversion efficiency = 90 %. Results retain the model limitations described above.

Common questions

Does this certify emergency lighting compliance?

No. It only calculates a simplified energy quantity under the supplied duration and losses.

Is three hours always required?

No universal duration is asserted here. Obtain the required duration from the applicable design and jurisdiction.

Can I use the full nominal battery capacity?

Only if that availability is justified. Aging, discharge rate, temperature and cutoff can reduce delivered energy.

Does battery capacity guarantee adequate escape-route lux?

No. Energy and photometric distribution are different requirements.

Which assumptions should I check?

Match the units, measurement plane and equipment boundary stated on this page. The starting values and comparison cases are chosen examples, not universal recommendations or current manufacturer ratings.

Where are the formula references?

Published references are listed at the bottom of this page as plain-text website addresses. The example tables are calculated from the displayed method rather than copied from proprietary tables.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.

  • Virginia Cooperative Extension: Estimating Appliance and Home Electronic Energy Usehttps://www.pubs.ext.vt.edu/2901/2901-9014/2901-9014.html
  • NIST SP 811 Appendix B.9: photometric unit conversionshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9