Lighting calculators / LED circuits & power
Plan the light. Understand the numbers.
LED Strip Power Supply Calculator
Use the full-on strip input per metre for the actual product, including the intended color-channel combination. A five-metre strip at 14.4 W/m requires 72 W nominally. Dividing by 24 V gives 3 A before any separate distribution losses. The selected headroom increases the candidate power figure without changing the strip’s nominal demand.
Your lighting inputs
Your result
Ready to calculateEnter your values and press Calculate. The result will open on the calculation page.
Published references · Clear assumptions · No sign-up
The method
Formula and calculation steps
Strip W = metres × W/m; current = W/V; candidate supply W = strip W × (1 + chosen headroom).
Calculate constant-voltage LED strip load and a stated supply-power allowance.
- Choose a measurement plane and use compatible units for all inputs.
- Obtain appropriate product data or representative measurements for the stated model.
- Submit the form, then interpret the result with the assumptions and limits below.
Headroom is a user assumption, not a universal manufacturer rule. Verify voltage, temperature derating, channel loading, wiring and product-specific operating limits.
12 V and 24 V strips, transformer sizing and LED drivers
Use the full-on strip input per metre for the actual product, including the intended color-channel combination. A five-metre strip at 14.4 W/m requires 72 W nominally. Dividing by 24 V gives 3 A before any separate distribution losses. The selected headroom increases the candidate power figure without changing the strip’s nominal demand.
Constant-voltage strips need a compatible voltage source; bare constant-current LED strings are different. Brand searches such as Ansell, Robus, BTF, Trex or specific landscape transformers still require the product documentation. This calculator does not validate dimmer protocols, waterproof ratings, manufacturer compatibility or thermal conditions.
Continue with: Lighting Power Density Calculator · General Lighting Load Calculator · Connected Lighting Load Calculator · LED Lighting Voltage Drop Calculator
Check the numbers
LED Strip Power Supply Calculator: calculated examples
These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.
Worked example with stated inputs
Total energized strip length = 5 m; Maximum input per metre = 14.4 W/m; Nominal constant voltage = 24 V; Chosen power headroom = 20 %.
| Output | Computed result |
|---|---|
| Supply power with chosen headroom | 86.4 W |
| Nominal strip input | 72 W |
| Nominal strip current | 3 A |
| Chosen headroom | 20 % |
How one input changes the answer
| Scenario | Changed input | Result |
|---|---|---|
| 1.25 m | Total energized strip length | 21.6 W |
| 2.5 m | Total energized strip length | 43.2 W |
| 3.75 m | Total energized strip length | 64.8 W |
| 5 m | Total energized strip length | 86.4 W |
| 7.5 m | Total energized strip length | 129.6 W |
| 10 m | Total energized strip length | 172.8 W |
| 15 m | Total energized strip length | 259.2 W |
Unchanged inputs use: Total energized strip length = 5 m; Maximum input per metre = 14.4 W/m; Nominal constant voltage = 24 V; Chosen power headroom = 20 %. Results retain the model limitations described above.
Common questions
Can I use this as a 12 V LED power supply calculator?
Yes for a constant-voltage load with a verified W/m rating. Enter 12 V and the actual strip data.
Is 20 percent headroom always required?
No. It is an editable planning choice. The exact supply’s derating and operating instructions control its use.
Does headroom fix voltage drop?
No. Distribution resistance and current cause voltage drop; assess the wiring and feed arrangement separately.
Can I use a constant-current driver for a 24 V strip?
Only if the product’s requirements explicitly match. Constant-current and constant-voltage systems are not interchangeable.
Which assumptions should I check?
Match the units, measurement plane and equipment boundary stated on this page. The starting values and comparison cases are chosen examples, not universal recommendations or current manufacturer ratings.
Where are the formula references?
Published references are listed at the bottom of this page as plain-text website addresses. The example tables are calculated from the displayed method rather than copied from proprietary tables.
Related calculators
Formula sources and references
References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.
- MEAN WELL: LED Driver Power Supply Solution, operating limits and loadinghttps://led.meanwell.com/qa.aspx?c=10
- NIST SP 811 Appendix B.9: photometric unit conversionshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9